NVIDIA has contributed its Vera Rubin rack and compute tray designs to the Open Compute Project (OCP), and said Meta will use its Spectrum-6 Ethernet switches while Google’s Falcon network protocol will come to future NVIDIA network cards. The company set out the announcements in a blog post on 12 October 2026 at the OCP Global Summit in San Jose; the descriptions of specifications and their benefits are NVIDIA’s and its partners’.
NVIDIA said it “contributed key NVIDIA Vera Rubin rack and compute tray designs to OCP through the open NVIDIA MGX architecture”. OCP is an industry group that shares open hardware designs for data centres; MGX is NVIDIA’s modular design for servers and racks. Vera Rubin is NVIDIA’s next AI computing platform.
MGX 1.2: racks up to 250kW
NVIDIA said the updated MGX 1.2 specification adds “rack-scale blind-mate liquid cooling, interoperable rack-scale interconnect infrastructure and a liquid-cooled 5,000A busbar designed for higher-power AI systems”. A busbar is a thick metal bar that carries power through the rack; blind-mate means parts connect automatically when slid into place. NVIDIA said MGX 1.2 also adds “native 19-inch equipment support” and “fanless liquid-cooled compute trays”, and “supports rack deployments up to 250kW”.
A rack design for Vera CPUs
NVIDIA also published a Vera CPU rack design specification. It said the rack “is designed to support tool calling, orchestration and sandboxed execution, helping AI agents interact with applications, data and services in real time”. NVIDIA described this as a design specification; the blog does not say Vera CPU racks are shipping.
Open standards for AI data centres and the grid
- Open Data Center Specification v0.7: NVIDIA said it “joined AMD, Google and Meta to publish” the spec, which “defines a unified blueprint for next-generation AI factory facility design — from power architecture to cooling infrastructure to physical layout”.
- OCP Grid Resilience Specification: formally the Interface Specification Between Hyperscalers and Utility Grid for Disturbance Performance, published by Google, Meta, Microsoft and NVIDIA, it sets out how large AI sites “should behave during utility grid disturbances: staying connected, responding automatically and restoring to near-full load within less than two seconds”.
NVIDIA also released open-source software for its DSX AI factory platform: Config Manager, Cluster Readiness Engine, Rack Management Service and a Cluster API Provider for NVIDIA Infrastructure Controller.
Meta adopts Spectrum-6
“Meta is adopting NVIDIA Spectrum-6 102.4Tb/s Ethernet switches to build larger, higher-performance NVIDIA Vera Rubin AI factories on open networking,” NVIDIA said. Meta’s Spectrum-6-based switch, N-IceCube, fits into IcePack, which NVIDIA describes as “Meta’s 100T, liquid-cooled rack”, and runs Meta’s open-source network software FBOSS.
NVIDIA said its Multiplane technology spreads GPU traffic “across up to eight independent network planes, enabling AI factories to scale beyond 100,000 GPUs with fewer switch tiers”. If one part fails, traffic moves to the remaining planes.
“Extending FBOSS to Spectrum ASICs means we can run that same software stack across our fabrics,” said Omar Baldonado, senior director of data center and AI networking at Meta.
Google’s Falcon on ConnectX-10
“NVIDIA and Google also announced Falcon Transport support on future NVIDIA ConnectX-10 SuperNICs and BlueField DPUs,” the blog said. Falcon is “a transport protocol designed to deliver data reliably over Ethernet networks, which can otherwise drop packets under congestion”. NVIDIA said NVIDIA and Google network cards will be able to talk over a common transport. No dates were given.
NVIDIA and Cisco’s new pluggable optics plan is covered separately: NVIDIA and Cisco plan USFP.
The grid specification is the part power networks will watch
Rack designs and switch deals will matter most to the companies that buy them. The grid document matters to everyone else on the electricity network. Its introduction says an event in North America in August 2024 caused “a simultaneous load loss of 1,500 MW” from the bulk power system, and that “a similar event of even larger magnitude” occurred in the Eastern Interconnection on 22 July 2026. When a cluster of data centres drops off the grid at once after a fault, the sudden surplus pushes frequency and voltage up, which is why utilities and regulators have been drafting stricter connection rules for large loads.
The specification is the hyperscalers’ answer. Google, Meta, Microsoft and NVIDIA commit their computing load, “typically ~70-90% of total data center load”, to ride through voltage dips and “restore to 90% of pre-fault load within 2 seconds”. The authors say the requirements “closely mirror” a proposal from ERCOT, the Texas grid operator, and follow a convention proposed by MISO, which runs much of the US Midwest grid. Cooling is left out: the authors say their experience suggests firmware upgrades “will not be sufficient” for cooling equipment to meet the ride-through requirements.
This is a constructive move. Large AI sites are becoming big enough to affect grid stability, and an industry-wide, published standard is easier for utilities to rely on than one-off promises. It also fits a wider trend: the UK has set five tests data centres must pass for faster grid connections. The gap is enforcement. An OCP specification is a voluntary commitment by its authors, and the rest of a site’s demand, up to 30% on the document’s own range, sits outside the two-second commitment.
The rest of the package shows how quickly Vera Rubin is moving into service. Oracle has since launched Vera Rubin on its cloud and Google Cloud has set a launch for its Vera Rubin A5X. Opening the rack designs through OCP lets other manufacturers build compatible hardware, but on NVIDIA’s own architecture, while rivals such as AMD are pitching their own open designs at the same summit, including the Helion rack for agentic AI.
Sources
- NVIDIA, “OCP Global Summit: Amid Ecosystem Adoption, NVIDIA Opens Vera Rubin Architecture to Help Scale AI Factories Worldwide”, NVIDIA blog, 12 October 2026. https://blogs.nvidia.com/blog/ocp-global-summit-vera-rubin-scale-ai-factories/
- Open Compute Project, “Interface Specification Between Hyperscalers and Utility Grid for Disturbance Performance”, version 1.0.0, effective 17 September 2026. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-Base-Spec-Interface-Specification-Between-Hyperscalers-and-Utility-Grid-for-Disturbance-Performance.pdf
- Open Compute Project, “Open Data Center: Next-Generation ML Infrastructure Design Principles”, revision 0.7.0, effective 27 August 2026. https://www.opencompute.org/wp-content/uploads/2026/10/Open-Data-center-Spec-Revision-0.7.0-4.pdf
Get TSN’s biggest tech stories, explained.
News and insights across AI, tech, crypto and cybersecurity. Every source linked. Unsubscribe anytime.
Get the newsletterRelated stories
- AM Intelligence’s extra 20,000 Nvidia Rubin GPUs: company plans for India and Malaysia
- NVIDIA GTC 2026: The $1 Trillion Infrastructure Bet Reshaping AI
- Lumentum, Astera Labs and Corning to Show PCIe Running Over Light Inside an AI Rack
- Arista Announces Ethernet Racks to Link Up to 144 AI Chips. Every Figure Is Arista’s Claim.
Follow @tsnmediahub on X for breaking AI news as it happens.
Follow on X