Public Register Now Lists 178 Data-Centre Fires and Power Failures

A public database of data-centre fires and power failures has nearly doubled in size in under two weeks, and the trend it appeared to show on 12 October has narrowed sharply as a result.

On 24 October the Energy Incident Register’s data-centre page listed 178 incidents across 40 countries, from 2010 to 2026. On 12 October, when DatacenterDynamics reported that such incidents had doubled since 2024, the same page gave 93 entries across 26 countries. Update, 1 November 2026: the register now lists 179 data-centre entries across 41 countries. The extra entry is dated 2023, so the 2024, 2025 and 2026 figures below (14, 18 and 21) are unchanged, as are the totals of 59 fires and 22 major incidents. The register says counts change for three reasons: new incidents are added as they are reported, older ones are added as its archive is worked through, and duplicate write-ups are merged.

The register logs incidents that start in a data centre’s power systems: battery rooms and UPS units (uninterruptible power supplies, which bridge the gap between a mains failure and generators starting), diesel generators and their fuel, switchgear and transformers. In its own words, “A software outage or a cooling fault with no fire or power failure is not recorded here.”

Data-centre fires and failures by year, then and now

When TSN first reported on the register, it listed 8 incidents in 2024, 20 in 2025 and 19 so far in 2026. The current figures are 14 for 2024, 18 for 2025 and 21 for 2026, with the year not yet over. Earlier years have grown too: 15 entries for 2023, 13 for 2022, 7 for 2021 and 6 for 2020, with 84 spread across 2010 to 2019. In total, 53 entries are dated 2024 or later.

Of the 178 entries, 59 are fires or thermal (overheating) events, and the register classes 22 as major, which it defines as “the longest outages, the worst damage and the incidents where people were hurt”.

Where public reporting names the failed part, the register counts the incident under each one. Battery rooms and UPS systems appear in 74 entries, generators in 56, switchgear in 30, transformers and substations in 18, and fuel systems in 6. In 54 entries the reporting does not say which part failed.

The United States has the most entries, 49, followed by the United Kingdom with 21, France with 11, Germany and Australia with 10 each, South Korea with 9, Japan with 8 and India with 6.

A London battery room shows what an entry looks like

One of the UK entries is a fire in the early hours of 24 January 2026 at a 13-storey tower housing a data centre on Nutmeg Lane in Blackwall, east London. The London Fire Brigade sent eight fire engines and around 60 firefighters after a first call at 04:52. The fire was limited to a string of lead acid batteries and was out by 06:43. The brigade said it was believed to be accidental, caused by the failure of one battery, and no one was hurt.

Not every entry is an equipment fault. Several from 2026 describe fires after strikes on facilities, including the 1 March incident in Amazon Web Services’ UAE region. AWS’s status updates said objects struck the data centre, “creating sparks and fire”, and that the fire department shut off power to the facility and its generators. Entries are also marked “Provisional” while details are confirmed, and the register sells paid records with fuller detail alongside its free list.

The doubling was mostly a filing backlog

The original headline, a rise from 8 incidents in 2024 to 20 in 2025, was accurate for the page as it stood on 12 October. It is no longer what the page says. Once older incidents were back-filled, 2024 gained six entries while 2025 now shows two fewer, leaving a rise from 14 to 18. That is an increase, but nothing like a doubling, and a register still working through its archive is a weak base for any trend line.

The more useful reading is about reporting, not frequency. Every entry depends on someone making an incident public: a fire service, a regulator, a news report or the operator itself. A count of data-centre fires and power failures that can move by 85 entries in twelve days measures the register’s own progress at least as much as the state of the industry. Comparing years only makes sense once the archive work is finished, and the register has not said when that will be.

The shape of the data has shifted too. On 12 October, 53 of 93 entries did not name the part that failed; now 54 of 178 do not, so almost all the added entries name one. The United States and the UK still lead the country list.

UPS batteries lead the named failures, as in Uptime’s survey

Battery rooms and UPS systems are the most frequently named part, in 74 of 178 entries, ahead of generators. An independent source points the same way. In its Annual Outage Analysis 2026, published in May, Uptime Institute found that power problems remained the leading cause of impactful outages, at 45% of those reported for 2025. Asked about the past three years, 39% of operators in its resiliency survey named UPS failure as a common cause of power-related outages, ahead of transfer switches (34%) and generators (28%). Uptime also says major fires at data centres have become gradually more frequent, with lithium-ion UPS batteries a clear contributing factor, though it adds that the rapid build-out of new sites may explain part of the rise. The two sources count different things, a public record of incidents against operators’ own survey answers, yet both put the backup power chain, not the servers, at the centre of the risk.

That matters because AI campuses are adding power equipment of every kind, from gas generators financed by Crusoe and Neuberger to the backup generation the US government let grid operator PJM call on in an October emergency order. Grid connections are a bottleneck too, as NextDC’s stalled works at its M3 Melbourne site showed. Cooling advances such as Vertiv’s direct-to-chip deployment in India fall outside this register unless a fire or power failure follows. The Blackwall fire began with a single failed battery and was out in under two hours, yet it still needed eight engines; how many such fires the public never hears about is the number no register can give.